Server and rack power connector guide

By the RackMatch team · Updated · Sources linked on the page

Every common plug and socket you meet in a rack, with ratings and where it is used. Printable version: one-page PDF cheat sheet.

Face view of IEC C13, C14, C19 and C20 connectors: C13/C14 have bevelled corners and upright pins, C19/C20 are rectangular with flat pins
C13/C14 vs C19/C20: shape, pins and ratings.
Diagram of which jumper joins a server PSU inlet to a PDU outlet: C13-C14, C19-C20, or C13-C20
Server inlet → jumper → PDU outlet.

IEC 60320 equipment connectors

These are the cords between equipment and the PDU or wall cord. The pair names always go odd (female) to even (male).

PairRatingHow it matesTypical use
C5 / C62.5 AC5 coupler into C6 inletLaptop power bricks ("cloverleaf")
C7 / C82.5 AC7 coupler into C8 inletSmall devices, some mini PCs and set-top boxes ("figure 8")
C13 / C1410 A IEC, 15 A ULC13 coupler into C14 inletMost 1U/2U servers, switches, storage, PCs, monitors. Most PDU outlets are C13
C15 / C1610 A, 120 °CC15 fits C16 and C14 inlets; C13 does not fit C16Hot-running gear, some network switches and kettles
C19 / C2016 A IEC, 20 A ULC19 coupler into C20 inletHigh-watt server PSUs (about 2000 W and up), GPU servers, PDU and UPS inputs
C21 / C2216 A, 155 °CC21 fits C22 and C20 inletsHigh-temperature version of C19/C20

Wall and PDU input plugs

PlugRatingRegionTypical use
NEMA 5-1515 A, 125 VNorth AmericaStandard US/Canada wall outlet
NEMA 5-2020 A, 125 VNorth America20 A outlet with a T-shaped neutral slot
NEMA L5-3030 A, 125 V, lockingNorth AmericaSome 120 V rack PDUs and UPS inputs
NEMA L6-2020 A, 250 V, lockingNorth America208/240 V rack PDUs
NEMA L6-3030 A, 250 V, lockingNorth AmericaCommon 208/240 V single-phase rack PDU input
NEMA L21-3030 A, 120/208 V 3-phase, lockingNorth AmericaThree-phase rack PDUs
IEC 60309 blue 2P+E16 A or 32 A, 200-250 VEurope, Africa, AsiaSingle-phase rack PDU inputs (e.g. 32 A, 7.4 kW at 230 V)
IEC 60309 red 3P+N+E16 A or 32 A, 380-415 VEurope, Africa, AsiaThree-phase rack PDU inputs
CEE 7/7 (Schuko)16 A, 250 VMost of EuropeWall outlet
BS 136313 A fused, 250 VUK, Ireland, parts of Africa/AsiaWall outlet
SANS 164-1 (Type M)15 A, 250 VSouth AfricaLarge round-pin wall outlet
SANS 164-2 (Type N)16 A, 250 VSouth Africa, BrazilNewer compact wall outlet

Rules that prevent wrong orders

  1. The inlet on the installed PSU decides the cord, not the server model. Read the PSU label.
  2. Odd numbers are the female end (coupler/outlet), even numbers the male end (inlet/plug): C13 goes into C14, C19 into C20.
  3. A C13 cord does not fit a C20 inlet. A C19 cord does not fit a C14 inlet.
  4. Cord current rating is set by its weakest end. A C13-to-C20 cord is still a 10 A cord.
  5. North America: load circuits to 80% of the breaker for continuous load (30 A circuit = 24 A usable).
  6. A/B feeds: plug each PSU into a different PDU on a different circuit. One PDU must carry the whole load alone.
  7. High-watt PSUs often give full power only on 200-240 V. On 120 V they are derated.

Next steps

Find the cord for one server and one PDU on the home page matcher. Size a PDU with the PDU calculator. Estimate running cost with the power cost calculator. Detail pages: C13 vs C14, C19 vs C20, C13 vs C19.

Cabling a whole rack? Build the full cord list and get a free quote.

How much power each connector carries

Theoretical maximum = volts × amps. North American circuits are limited to 80% for continuous load. Real PSUs should run well below these numbers.

ConnectorRatingat 120 Vat 208 Vat 230 V
C13 / C1410 A IEC, 15 A UL1.8 kW (15 A)3.1 kW (15 A)2.3 kW (10 A)
C19 / C2016 A IEC, 20 A UL2.4 kW (20 A)4.2 kW (20 A)3.7 kW (16 A)
NEMA L6-30 input30 A, 250 V—6.2 kW (5.0 kW continuous)—
IEC 60309 blue 32 A input32 A, 230 V——7.4 kW

Locking connectors

Locking C13 and C19 cords stop a cord from being pulled out by accident in a dense rack. Some lock with a latch on the cord, others need a PDU with locking outlets. Vendors use different systems, so check that the locking cord and the PDU outlet are made to work together. A normal cord still fits a locking outlet; it just does not lock.

Reading cord markings

Frequently asked questions

Which numbers are male and which are female?

In IEC 60320 the odd number is the female end (coupler or outlet) and the even number is the male end (inlet or plug). C13 mates with C14, C19 with C20.

What is the most common rack connector?

C13/C14. Most PDU outlets are C13 and most 1U/2U server PSUs have C14 inlets.

What plug does a 208 V rack PDU use in the US?

Often NEMA L6-30 (30 A, 250 V, locking) for single-phase, or L21-30 for three-phase.

What plug does a 32 A PDU use in Europe or Africa?

Usually an IEC 60309 blue 2P+E 32 A plug for single-phase, or red 3P+N+E for three-phase.