Dell PowerEdge R760 + Raritan PX3-5496V Power Cable
Not compatible for the 2400 W PSU. No standard jumper.
| Connector | Server C20 inlet needs a C19 outlet on the PDU. PX3-5496V has C13 only |
| Voltage / current | Server PSU 200–240 V / 16 A vs PDU C13-only, 208 V, 30 A (24 A rated) |
| Locking | n/a |
Why there is no match
Raritan lists PX3-5496V as 24 × C13. There is no C19. A R760 PSU here uses a C20 inlet. C13 will not plug into C20, and the C13 path is 10 A class against a 16 A class inlet.
Fix: a PDU with C19 outlets and an IEC C19–C20 jumper. Example on this site: R760 + AP8853. See also C13 PDU, C19 server.
C13 outlet is 10 A class. This PSU inlet is 16 A class. Do not use a cheater adapter.